Improving acoustics in sports halls: stretch ceilings as the key solution
With one caveat: a stretch ceiling is not suitable for the playing area. Where it makes sense in a sports facility, what to use above the court instead, and how much absorption each option provides.
For designers and managers of sports facilities who are considering a stretch ceiling.
You often hear that a stretch ceiling is the key to a hall's acoustics. That is too much of a simplification. A smooth PVC membrane barely absorbs sound, so it will not shorten reverberation. Nor is it a ball-impact resistant ceiling, and in a sports hall that is a basic requirement.
That does not mean a membrane has no place in a sports facility. It does, but only where the ball cannot reach, and only in the acoustic version. Below: where that is, and what to use in its place above the court.
Three ceilings, one surface area: 300 m²
Absorption area is surface area times the absorption coefficient. Reverberation-chamber measurements of the membrane (ISO 354) give NRC 0.05 for smooth film, 0.45 for micro-perforated, and 0.80 for micro-perforated with 40 mm of mineral wool above it. A class A tile has an αw of at least 0.90. For a 300 m² ceiling, this gives:
Scroll horizontally to see all columns
Above the court: a ceiling tested with a ball
Impact resistance is tested for the whole assembly, meaning the tiles together with the grid and clips, according to PN-EN 13964, Annex D. The result is class 1A, 2A or 3A. In the Ecophon Super G family, Super G Plus A and Super G B are class 1A, while Super G A is 2A and 3A. All three have absorption class A. The glass wool core of Super G A has a reaction to fire of A2-s1,d0. The best membranes reach B-s1,d0, typical ones B-s2,d0.
A membrane has none of these classes: no test has confirmed that it will withstand a ball hit and stay in its profile. We describe how to choose the right class in our sports hall acoustics service.
Where a membrane makes sense
Entrance halls, receptions, cafés and conference rooms next to the hall — wherever appearance matters and the ball does not reach.
Rooms with an unusual shape (arches, domes) that cannot easily be covered with tiles.
Always in the micro-perforated version, ideally with mineral wool above the membrane. The smooth version does nothing for acoustics, as the table above shows. More in our guide on how stretch ceilings affect acoustics.
Frequently asked questions
Will a stretch ceiling withstand a ball hit?
You should not count on it. A membrane has no impact resistance class under PN-EN 13964, so above the court you need a ceiling that does, for example from the Ecophon Super G family.
What if the hall ceiling is very high?
Height reduces the risk but does not remove it: a volleyball or football can fly high. For high-mounted ceilings a lower class (2A instead of 1A) is often enough, but some class is still required, and a membrane has none.
Does a hall only need a new ceiling?
Usually not. Between parallel bare walls a flutter echo arises that a ceiling will not remove. That is why the design also covers selected walls, again with impact-resistant panels.
Sources
- C. Nocke, C. Hilge, J.-M. Scherrer — Micro-perforated sound absorbers in stretched materials, Acoustics 2011 (measurements per ISO 354)(opens in a new tab)
- Ecophon Super G — variants and impact resistance classes (EN 13964, Annex D)(opens in a new tab)
- Ecophon Super G A — product data sheet (2024-05-16): absorption, reaction to fire, impact classes(opens in a new tab)