The art of noise reduction: how to improve acoustics in existing sports halls
Retrofitting an existing hall in five steps: measurement per ISO 3382-2, calculating the missing absorption, ceiling plus walls, impact resistance and a measurement after installation. With an example for a 5184 m³ hall.
For hall managers and contractors who need to improve the acoustics of a facility that is already in use.
In an existing hall there is no need to guess how bad things are. You can measure it and, from the measurement, calculate how much sound-absorbing material is missing. The order matters: whoever starts by buying panels usually buys too many or too few and installs them in the wrong places.
Echo is reduced by absorption. Sound-reflecting materials and “noise-cancelling” electronics will not shorten reverberation in a large hall. Below is the order of work we follow.
Step 1: measurement before
Reverberation time is measured according to PN-EN ISO 3382-2. For comparison with the requirements, the engineering method is used: at least 2 sound source positions and at least 6 independent source–microphone combinations. The microphones stand roughly 2 m apart and about 1 m from the walls and floor, and the result is given in octave bands from 125 to 4000 Hz. The hall is measured empty.
Step 2: the calculation – how much is missing
Example: a 36 × 18 × 8 m hall, i.e. V = 5184 m³. That is more than 5000 m³, so the target under PN-B-02151-4 is 1.8 s. Suppose the measurement gave 4.0 s in the 500 Hz band.
From Sabine’s formula (A = 0.161 × V / T), the current absorption is 0.161 × 5184 / 4.0 ≈ 209 m², and the required absorption is 0.161 × 5184 / 1.8 ≈ 464 m². About 255 m² is missing. A class A panel (αw ≥ 0.90) laid in place of a hard surface (assume α ≈ 0.05) adds about 0.85 m² of absorption per square metre. So 255 / 0.85 = 300 m² of material is needed, i.e. 46% of the 648 m² ceiling.
On paper, almost half of the ceiling would be enough. In practice, the calculation is repeated for each band, and the hardest is usually 125 Hz. That is why designs include a margin, and a suspended ceiling with an air cavity helps with low frequencies more than panels glued to the slab.
Steps 3–5: layout, impact resistance, measurement after
Ceiling and walls. Sound also reflects horizontally, between parallel walls. In a rectangular hall, about 70–80% of the ceiling and 10–20% of the walls are specified with material of αw ≥ 0.9, so that each of the three pairs of parallel surfaces has an absorbing area.
Impact resistance. The ceiling and panels within reach of the ball must be class 1A, 2A or 3A under PN-EN 13964, tested for the complete assembly with the grid and clips. In an existing hall you also need to check that the slab or roof can carry the new structure.
Installation during a break. Work is usually carried out during school holidays, when the hall is free.
Measurement after. The same method and the same positions as before installation. Only comparing the two measurements shows what the investment actually delivered. An example of a retrofit completed with post-installation measurements: sports hall in Babimost.
Frequently asked questions
Does an existing hall have to meet the reverberation standard?
If it is being rebuilt or its use changes – yes, because the technical regulations then apply. If nothing is being altered, the regulation does not force an improvement. Still, it is worth using the limit from PN-B-02151-4 as a design target.
Is it enough to hang panels on one wall?
Usually not. One wall is not enough in a large volume, and the bare opposite wall still forms a reflecting pair with the first. The layout follows from the calculation and the hall’s geometry – that is a job for an acoustic study.
How much does it cost to quieten a hall?
An impact-resistant ceiling costs from PLN 300/m² net; wall panels are added on top. The exact amount depends on the area, the impact class and the height of the hall – more in the sports hall acoustics offer.
Sources
- ISO 3382-2:2008 — Acoustics. Measurement of room acoustic parameters. Part 2: Reverberation time in ordinary rooms (standard preview: Table 1, clauses 4.3 and 5.1)(opens in a new tab)
- Ecophon — Polish Standard PN-B-02151-4:2015-06. Explanations and commentary (requirements and guidance for sports halls)(opens in a new tab)