For designers
The most common mistakes in sports hall acoustic design
Ceiling only, no impact class, forgotten bass, wrong volume and no measurement after installation. Five mistakes that leave a hall booming even after treatment — each with a number you can check.
For designers who want the hall to pass the acceptance measurement the first time.
The requirement is simple: PN-B-02151-4:2015-06 allows a reverberation time of up to 1.5 s in a sports hall with a volume up to 5000 m³, and up to 1.8 s above that. Even so, a hall sometimes still booms after treatment. The cause is rarely the wrong material — more often a design that overlooked one of several obvious things.
Below are the five mistakes we meet most often, and the numbers that let you catch them at the design stage.
Mistakes 1–2: ceiling only, and no impact class
The ceiling alone is not enough. The commentary to the standard says it outright: sound-absorbing material should be placed on each of the three pairs of parallel surfaces — in practice on 70–80% of the ceiling and 10–20% of the walls (αw ≥ 0.9). Without wall panels, flutter echo remains between the walls — which is why our sports hall acoustics covers the ceiling and selected walls.
The second mistake is a material without an impact resistance class per PN-EN 13964, Annex D, or with a class that is too low. Even within one product family the difference can be large: Super G A has classes 2A and 3A, while Super G Plus A has 1A. The class is chosen to suit the installation location and the sports played, and confirmed for the whole system, not just the panel.
Mistake 3: forgotten low frequencies
The standard checks the hall's reverberation time in the bands from 250 Hz to 4 kHz, but its commentary warns that halls usually lack absorption in the 125 Hz band. The hall can then meet the requirement in the speech range and still boom in the low tones.
An air cavity above the ceiling helps. The same Super G A 35 mm panel absorbs 0.15 in the 125 Hz band at a system depth of 50 mm and 0.50 at 200 mm. So specify not only the product in the design, but also the suspension height.
Mistakes 4–5: class instead of area, no measurement
What counts is the equivalent absorption area A = S × α, not the class alone. 400 m² of material with αw 1.00 gives 400 m², while 500 m² of material with αw 0.85 gives 425 m². Class A on too small an area loses to class B on a larger one.
Watch the volume threshold too. A 36 × 18 m hall with a height of 7.5 m has 4860 m³ and must reach 1.5 s; the same hall 8 m high has 5184 m³ and 1.8 s is enough. Half a metre of height changes the requirement — calculate the volume from the design, not “by eye”.
The last mistake is no measurement after installation. The requirement applies to the finished and equipped hall without people, so only a reverberation time measurement (per PN-EN ISO 3382-2) confirms that the design worked.
Frequently asked questions
Is it enough to cover the whole ceiling with class A material?
Usually not. The commentary to the standard recommends material on 10–20% of the walls as well, because the ceiling alone does not break up reflections between parallel walls.
In which bands does the standard check a hall's reverberation?
In the octave bands from 250 Hz to 4 kHz, in the finished room without people. The 125 Hz band is not required, but it is worth taking care of.
Who should calculate the amount of material?
The acoustician, as part of an acoustic study — based on the volume, the building materials and the target reverberation time. That is cheaper than corrections after a failed measurement.
Sources
- Ecophon — Polska Norma PN-B-02151-4:2015-06. Objaśnienia i komentarze (requirements, bands and guidance for sports halls)(opens in a new tab)
- Saint-Gobain Ecophon — Ecophon Super G A datasheet (2024-05-16): absorption by band, impact classes(opens in a new tab)
- Saint-Gobain Ecophon — Super G family: impact classes of the variants(opens in a new tab)